Publication 1747-UM010B-EN-P - September 2003

A-8 Specifications

Determining T

SNo-bt

Use the following table to find T

SNo-bt

for your particular

configuration.

Determining T

btx

Before determining (T

btx

),

you need to establish the maximum BT

write or read length that is to be processed by each logical rack on the
RIO link. RIO scan time is increased each time an BT is sent to any
logical device on the RIO network. The scan time increase depends
on the number of words sent in the BT and the selected baud rate.

RIO link protocol allows for a maximum of one BT to be sent to each
logical rack on the RIO link during any single RIO scan. Therefore, if
multiple BTs are sent to devices within the same logical rack, only the
longest BT to that logical rack needs to be considered to determine
your maximum throughput. The RIO scan time increase (T

ri

) for each

logical rack is:

IMPORTANT

The times shown are, to the best of our knowledge,
the maximum delay times of the backup scanner.
However, in instances that throughput is an important
consideration, test the application thoroughly first to
ensure proper operation. Note that in most situations
the average throughput is much better than the
calculated maximum throughput.

Number of
Logical Racks
Configured

Normal Mode

Complementary Mode

All Baud Rates

57.6K baud

115.2K baud

230.4K baud

1 Logical Rack

16.0

19.0

24.0

32.0

2 Logical Racks

19.0

23.0

27.0

36.0

3 Logical Racks

22.0

26.0

30.0

39.0

4 Logical Racks

25.0

28.0

34.0

42.0

Baud Rate

RIO Scan Time Increase (T

ri

)

57.6K baud

0.300 x BT length + 5.0 ms

115.2K baud

0.150 x BT length + 3.5 ms

230.4K baud

0.075 x BT length + 2.0 ms