M0-M1 Files and G Files B-5
SLC 5/02 Processor Example
If you are using a SLC 5/02 Series B processor, add 1930 µs to the
program scan time for each bit instruction addressed to an M0 or M1
data file. If you are using a SLC 5/03 Series C processor, add 1160 µs.
If you are using a SLC 5/02 Series B processor, add 1580 µs plus
670 µs per word of data addressed to the M0 or M1 file. As shown
above, 34 words are copied from #B3:0 to M0:1.0. Therefore, this
adds 24360 µs to the scan time of the COP instruction. If you are
using a SLC 5/02 Series C processor, add 950 µs plus 400 µs per word.
This adds 14550 µs to the scan time of the COP instruction.
SLC 5/04
SLC 5/05
XIC or XIO
743 µs
—
OTU, OTE, or
OTL
879 µs
—
COP to M file
—
735 µs plus 23 µs per word
COP from M file
—
722 µs plus 22 µs per word
FLL
—
716 µs plus 30 µs per word
MVM to M file
850 µs
—
any source or
Destination
M file address
694 µs
—
(1) Except the OSR instruction and the instruction parameters noted on page B-2.
Processor
Instruction
Type
Access Time
per Bit
Instruction or
Word of Data
Access Time per
Multi-Word Instruction
M0:2.1
1
M1:3.1
1
M0:2.1
10
COP
Copy File
Source
#B3:0
Dest
#M0:1.0
Length
34
COP