Backup scanner installation, Backup scanner installation -4 – Rockwell Automation 1747-BSN Backup Scanner Module User Manual
Page 46

Publication 1747-UM010B-EN-P - September 2003
3-4 Installation and Wiring
The figure below shows the location of the DIP switches on the
Backup Scanner.
Backup Scanner
Installation
Installation procedures for this module are the same as for any other
discrete I/O or specialty module. Refer to the illustration on page 3-5
to identify chassis and module components listed in the procedures
below.
IMPORTANT
For proper RIO link system operation, all devices
must be configured for the same baud rate.
1 2 3 4
O
N
1 2 3 4 5 6
O
N
1 2 3 4
1 2 3 4 5 6
Module Address Switch
Configuration Switch
ATTENTION
!
Disconnect system power before attempting to install,
remove, or wire the backup scanner.
IMPORTANT
Make sure you have set the DIP switches properly
before installing the scanner.
IMPORTANT
Before installation, ensure that your modular SLC
power supply has adequate reserve current capacity.
The scanner requires 800 mA at 5V dc.