1-12 Overview

Guidelines for Configuring Complementary I/O

When you configure your remote system for complementary I/O,
follow these guidelines:

•

You can place an output module in the primary chassis opposite
another output module in the complementary chassis; they use
the same bits in the output image table. However, we do not
recommend this placement of modules for redundant I/O.

•

You cannot use complementary I/O with a chassis that uses
32-point I/O modules and 1-slot addressing or 16-point I/O
modules with 2-slot addressing.

•

Do not place an input module in the primary chassis opposite
an input module in the complementary chassis because they use
the same bits in the input image table.

2-Slot Addressing

The figures below illustrate a possible module placement to configure
complementary I/O using 2-slot addressing.

I
8

O

8

I
16

I
8

I
8

O

8

O

16

O

8

O

BT

BT

8

O

8

O

8

O

8

I

8

I

8

I

8

I

8

O

8

1

0

1

2

3

4

5

I

16

I

16

I

16

O

16

O
16

O
16

0

1

2

3

4

5

I

16

I

16

I

16

O

16

O

16

O
16

1

E

M

P
T

Y

Outputs in the complementary chassis would use the same bits in the

output image table as the outputs in the primary chassis. You cannot

place inputs in the complementary chassis.

E

M

P
T
Y

E

M

P
T
Y

E

M

P
T
Y

E

M

P
T
Y

Primary

I = Input Module (8- or 16-point)
O = Output Module (8- or 16-point)
BT = Block Transfer Module

Primary

Complementary

Complementary

(1) Must be empty if corresponding primary slot is a block transfer module.

IMPORTANT

With 2-slot addressing, if an input module resides in
either slot associated with a logical group of the
primary chassis, an input module cannot reside in
that logical group's complementary chassis.