Rockwell Automation 1734-8CFG POINT I/O Module with 8 Configurable 24V DC Points IN User Manual
Page 16

16 POINT I/O Module with 8 Configurable 24V DC Points
Publication
1734-IN038A-EN-P - October 2008
In RSLogix5000, the default tags will be:
•
AdapterName:SlotNumber:C.FilterOffOn
•
AdapterName:SlotNumber:C.FilterOnOff
•
AdapterName:SlotNumber:C.PtPointNumberFaultMode
•
AdapterName:SlotNumber:C.PtPointNumberFaultValue
•
AdapterName:SlotNumber:C.PtPointNumberProgMode
•
AdapterName:SlotNumber:C.PtPointNumberProgValue
Default Data Map - Configuration Assembly Instance 103
Message Size: 8 Bytes
7
6
5
4
3
2
1
0
Data [0]
Group Off2On Input filter
Data [1]
Data [2]
Group On2Off Input filter
Data [3]
Data [4]
FltM 7
FltM 6
FltM 5
FltM 4
FltM 3
FltM 2
FltM 1
FltM 0
Data [5]
FltV 7
FltV 6
FltV 5
FltV 4
FltV 3
FltV 2
FltV 1
FltV 0
Data [6]
IdlM 7
IdlM 6
IdlM 5
IdlM 4
IdlM 3
IdlM 2
IdlM 1
IdlM 0
Data [7]
IdlV 7
IdlV 6
IdlV 5
IdlV 4
IdlV 3
IdlV 2
IdlV 1
IdlV 0
Where:
Filter = 0 to 65000 ms (0 = default)
Filter = 0 to 65535 ms (1000 = default)
FltM = Fault Mode (0 = Fault Value (default), 1 = Hold Last State)
FltV = Fault Value (0 = OFF (default), 1 = ON)
IdlM = Idle Mode (0 = Idle Value (default), 1 = Hold Last State)
IdlV = Idle Value (0 = OFF (default), 1 = ON)