Rockwell Automation 1734-8CFG POINT I/O Module with 8 Configurable 24V DC Points IN User Manual
Page 18

18 POINT I/O Module with 8 Configurable 24V DC Points
Publication
1734-IN038A-EN-P - October 2008
Network
status
Off
Device is not online.
- Device has not completed dup_MAC_id test.
- Device not powered - check module status indicator.
Flashing green
Device is online but has no connections in the
established state.
Green
Device is online and has connections in the
established state.
Flashing red
One or more I/O connections in timed-out state.
Red
Critical link failure - failed communication device.
Device detected error that prevents it communicating
on the network.
Flashing red/green
Communication faulted device - the device has
detected a network access error and is in
communication faulted state.
Device has received and accepted an Identify
Communication Faulted Request - long protocol
message.
I/O status
Off
Input is in the OFF state.
Output is in the OFF state.
Yellow
Input is in the ON state.
Output is in the ON state.
Indicator
State
Description