Ground the 1769-og16 module, Remove the finger-safe terminal block – Rockwell Automation 1769-OG16 Compact TTL Output Module User Manual
Page 12
 
12 Compact TTL Output Module
Publication 1769-IN078A-EN-P - May 2006
Ground the 1769-OG16 Module
This product is intended to be mounted to a well-grounded mounting surface such 
as a metal panel. Additional grounding connections from the module’s mounting 
tabs or DIN rail (if used) are not required unless the mounting surface cannot be 
grounded.
Refer to Industrial Automation Wiring and Grounding Guidelines, Allen-Bradley 
publication 1770-4.1, for additional information.
A removable, write-on label is provided with the module. Remove the label from 
the door, mark the identification of each terminal with permanent ink, and slide the 
label back into the door. Your markings (ID tag) will be visible when the module 
door is closed.
Ground the Module
Remove the Finger-safe Terminal Block
To remove the terminal block, loosen the upper and lower retaining screws. The 
terminal block will back away from the module as you remove the screws. When 
replacing the terminal block, torque the retaining screws to 0.46 Nm (4.1 in-lbs).
Wire the 
finger-safe 
terminal block.
Upper Retaining Screw
Lower Retaining Screw