Fault State Word
Word 3, the fault state word, selects the hold last
state or user-defined safe state condition for each
individual output on a system transition from Run
to Fault.
Fault Value Word
The fault value word, word 4, is used to program
the fault state value (0 = Off, 1 = On). Each
output is individually configurable for on or off.
Program to Fault Enable Bit (PFE)
Word 0, bit 0, allows the selection of which data
value, the program or fault value, to apply to the
output if a system in Program mode undergoes a
system fault, resulting in a change to the Fault
mode.
Module Default Condition
(1)
The modules default condition is all zeros.
(1)
TTL outputs are inverted (On = 1 = logic low voltage = 0…0.4V dc; Off = 0 = logic high voltage = 4.5…5.5V dc). Use a NOT
instruction in the ladder program to convert to traditional True = High logic.
Programming Conditions
Word or Bit Affected
Condition Applied
Word 0, Bit 0
Program-to-fault Enable
Program Value
Word 1
Program State
User-defined Safe State
Word 2
Program Value
Off
Word 3
Fault State
User-defined Safe State
Word 4
Fault Value
Off
Condition Bit
Setting
User-defined Safe State
0
Hold Last State
1
Value
Bit Setting
Off
0
On
1
Value Applied
Bit Setting
Program
0
Fault
1