Fault state word, Fault value word, Program to fault enable bit (pfe) – Rockwell Automation 1769-OG16 Compact TTL Output Module User Manual

Page 16: Module default condition, Fault value wo rd, Programming conditions

Advertising
background image

16 Compact TTL Output Module

Publication 1769-IN078A-EN-P - May 2006

Fault State Word

Word 3, the fault state word, selects the hold last
state or user-defined safe state condition for each
individual output on a system transition from Run
to Fault.

Fault Value Word

(1)

The fault value word, word 4, is used to program
the fault state value (0 = Off, 1 = On). Each
output is individually configurable for on or off.

Program to Fault Enable Bit (PFE)

Word 0, bit 0, allows the selection of which data
value, the program or fault value, to apply to the
output if a system in Program mode undergoes a
system fault, resulting in a change to the Fault
mode.

Module Default Condition

(1)

The modules default condition is all zeros.

(1)

TTL outputs are inverted (On = 1 = logic low voltage = 0…0.4V dc; Off = 0 = logic high voltage = 4.5…5.5V dc). Use a NOT
instruction in the ladder program to convert to traditional True = High logic.

Programming Conditions

Word or Bit Affected

Condition Applied

Word 0, Bit 0

Program-to-fault Enable

Program Value

Word 1

Program State

User-defined Safe State

Word 2

Program Value

Off

Word 3

Fault State

User-defined Safe State

Word 4

Fault Value

Off

Condition Bit

Setting

User-defined Safe State

0

Hold Last State

1

Value

Bit Setting

Off

0

On

1

Value Applied

Bit Setting

Program

0

Fault

1

Advertising