Wire the finger-safe terminal block, Configure the 1769-og16 module, Output data file – Rockwell Automation 1769-OG16 Compact TTL Output Module User Manual

Page 13

Advertising
background image

Compact TTL Output Module 13

Publication 1769-IN078A-EN-P - May 2006

Wire the Finger-safe Terminal Block

When wiring the terminal block, keep the finger-safe cover in place.

1. Loosen the terminal screws to be wired.

2. Route the wire under the terminal pressure plate.

You can use the bare wire or a spade lug. The terminals will accept a
6.35 mm (0.25 in.) spade lug.

3. Tighten the terminal screw making sure the pressure plate secures the wire.

Recommended torque when tightening terminal screws is 0.68 Nm (6 in-lb).

Configure the 1769-OG16 Module

The following I/O memory mapping lets you configure the 1769-OG16 module.

Output Data File

For each module, slot x, word 0 in the output data file contains the state of the
module’s output points. The module implements inverted logic on the TTL outputs.
An Output Data File bit set to 1 results in a logic low output voltage on the
corresponding output point. An Output Data File bit cleared to 0 results in a logic

high output voltage on the corresponding output point.

TIP

The terminal screws are non-captive. Therefore, it is possible to use a ring lug
[max 1/4 in. o.d. with a 0.139 in. minimum i.d. (M3.5)] with the module.

TIP

If you need to remove the finger-safe cover, insert a screwdriver into one of the
square, wiring holes and gently pry the cover off. If you wire the terminal block
with the finger-safe cover removed, you will not be able to put it back on the
terminal block because the wires will be in the way.

Output Data File

Wo

rd

Bit Position

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

0

w

(1)

(1)

w = write.

w

w

w

w

w

w

w

w

w

w

w

w

w

w

w

Advertising