ArmorBlock LP2 16 Sourcing Output Module

3

1792D-5.49 - August 1999

Install Your ArmorBlock LP2 I/O Module

To install the module:

• Mount the module and attach the unit to the DeviceNet trunk.

• Set the node address and baud rate.

• Connect the output cord sets to the LP2 module.

• Communicate with your ArmorBlock LP2 module.
More detailed information about each of these steps is in the following
procedures.

Mount the Module and Attach the Unit to the Devicenet Trunk

1. Mount the module using the dimensions shown below.

2. Connect the grey DeviceNet cable to the DeviceNet trunk. Use the

1485P-P1R5-MN5R1 T-Part tap to make the connection to round
media. Use the 1485P-P1E4-R5 to connect to the Kwik Link flat media
system.

3. Connect the black auxiliary power cable to your 24V dc power source.

Set the Node Address and Baud Rate

Set the node address using RSNetWorx for DeviceNet

™ software,

DeviceNetManager

™ software, or another software configuration tool. The

module is equipped with AutoBaud detect. AutoBaud lets the module read
the settings already in use on your DeviceNet network and automatically
adjusts to follow those settings.

O-4

O-5

O-6

O-7

O-11

O-10

O-2

O-3

O-13

O-12

O-9

O-8

Network Status

Module Status

O-0

O-1

O-15

O-14

Auxiliary Power

42049

4.21in

107mm

0.25in

6.25mm

12in

305mm

1.95in

49.5mm

6.85in

174mm

2.7in

68.5mm

(width)