16 Output Module - Cat. No. 1792D-OBT16LP

Sourcing Output Specifications

Max

Min

Outputs per block

16 sinking outputs labeled 00 through 15

Output Auxiliary Voltage

30V

10V

On-state Voltage Drop

1V

-

On-state Current

0.3A

-

Off-state Leakage

1.5mA

-

Module Current (all outputs)

4.0A

-

Surge Current - for 10 ms,
repeatable every 2s

0.6A

-

Indicators

Network Status - red/green
Module Status - red/green
Auxiliary Power - green
Point LED - yellow

Communication Rate

• 125Kbps @ 500 meters(1600 feet) for thick

cable, flat media length 375 meters

• 250Kbps @ 200 meters(600 feet) for thick

cable, flat media length 150 meters

• 500Kbps @ 100 meters (330 feet) for thick

cable, flat media length 75 meters

DeviceNet Power Voltage
Current

25V dc
125mA

11V dc
250mA

Auxiliary Power

Voltage
Current

30V dc
4A

10V dc
4A

Dimensions (assembled to base)
inches - (Millimeters)

1.023H x 2.7W x6.85D
(26)H x (68.5)W x (174)D

Environmental Conditions
Operational Temperature
Storage Temperature
Relative Humidity
Shock Operating
Non-operating
Vibration

-25 to 60

o

C (-13 to 140

o

F)

-25 to 80

o

C (-13 to 176

O

F)

Up to 100%
30g peak acceleration, 11 (+1) ms pulse width
50g peak acceleration, 11(+1)ms pulse width
Tested 10g @ 10-500Hz per IEC 68-2-6

Conductors

Publication DN-6.7.2

Enclosure

Meets or exceeds IP67

Agency Certification
(when product is marked)

• CE marked for all applicable directives