Connect the Output Cord Sets to the LP2 Module

This module uses 5 pole micro (12mm) style PCB mounted connectors.

Eight micro caps cover the connectors on your module. Remove the caps
and connect your cables to the appropriate ports. This product has two
outputs per connector. Use a “Y” splitter cable for access to all output
connections. For more information on these cables, see the Product Data
guide, publication 1792-2.1.

Use the micro caps to cover and seal unused ports. A pinout diagram for
the connectors is shown below.

!

ATTENTION:

• Make sure all connectors and caps are securely tightened

to properly seal the connections against leaks and
maintain IP67 requirements.

• For maximum noise immunity, output cable return wires

must be properly terminated. When outputs are
connected in loopback, return wires should be connected
together.

• I/O cable length should be less than 30 meters.

1

5

3

4

2

Output Micro-Connector

(View into Sockets)

Pin 1 Not Used
Pin 2 Output B
Pin 3 Auxiliary Power Return
Pin 4 Output A
Pin 5 Not Used