Rio device configuration -2, Rio device configuration – Rockwell Automation 1747-ASB Remote I/O Adapter User Manual
Page 106

Publication 1747-UM006B-EN-P - June 2003
8-2 Application Examples
The application is illustrated below. When the switch is closed, bulbs
1 and 2 turn on and an analog signal is moved to analog module
output 1, which leads to the meter.
RIO Device Configuration
The 1747-ASB module is configured in the following manner.
SLC 5/02
17461-OW8
1746-NIO4I
1747-SN
ASB
1746-OA16
1746-IA16
0
1
2
3
0
1
2
3
4
5
6
1746-IA16
1746-IA16
1746-OA16
1746-OA16
The meter is connected
to output 1.
The switch is connected
to input 15.
Bulb 2 is connected to
output 12.
Bulb 1 is
connected to
output 4.
Function
1747-ASB Module 1
Starting logical rack number
0
Starting logical group number
0
Image size (number of logical groups)
6
Addressing mode
1-slot
Specialty I/O mode
(1)
Discrete
Baud rate
230.4K
Last chassis
Yes
Hold last state
Yes
Processor restart lockout
Yes
Link response
(2)
Switch position does not
matter
Primary/complementary chassis
Complementary
(1) The 1747-SN Series A scanner cannot perform block transfers. Any specialty I/O modules
controlled by this scanner must be discretely mapped.
(2) Link response does not matter at 230.4K baud.