Link response time dip switch setting, Last chassis, On off – Rockwell Automation 1747-ASB Remote I/O Adapter User Manual
Page 73

Publication 1747-UM006B-EN-P - June 2003
Configuration 4-19
Link Response Time DIP Switch Setting
The 1747-ASB module is shipped from the factory with the default
position ON (restricted).
Last Chassis
SW3 switch 4 is used for last chassis selection when the 1747-ASB
module is connected to a PLC-2, PLC-5, or SLC scanner (Catalog
Number 1747-SN)..
The 1747-ASB module is shipped from the factory with the default
position ON (not last chassis).
A 1747-ASB module should be configured as the last chassis when:
•
Its image crosses logical rack boundaries and no other adapter
uses a higher group number within its last logical rack.
•
It uses a portion of a logical rack and no other adapter uses a
higher group number within that logical rack.