Save mode -2 check mode -2, Save mode, Check mode – Rockwell Automation 1747-ASB Remote I/O Adapter User Manual

Page 88

Advertising
background image

Publication 1747-UM006B-EN-P - June 2003

6-2 Start-Up and Operation

Save Mode

When power is applied in save mode, the 1747-ASB module:

1. Performs power up diagnostics

2. Reads and verifies the actual DIP switch and I/O module

configuration

3. Saves the DIP switch and I/O module configuration

4. Waits for RIO link communications from the scanner

Check Mode

When power is applied in check mode, the 1747-ASB module:

1. Performs power up diagnostics

2. Verifies the stored configuration integrity

3. Compares the actual DIP switch, I/O module and chassis

configurations to the stored configurations

4. Waits for RIO link communications from the scanner

1747-ASB module errors found during powerup and initialization are
noted in chapter 7.

After successfully completing a powerup and initialization sequence,
the 1747-ASB module waits to receive RIO link communications from
the scanner for all of its logical devices. Once the 1747-ASB module
receives RIO link communication for all of its logical devices, it begins
normal operation.