DH485/RS-232C Interface Module 9

Publication 1747-IN006B-EN-P - October 2005

Set the Module’s Functionality

Setting the module’s mode depends on which method you want to use to configure
the module. You can configure the module using an ASCII terminal or backplane
communication.

Configure the Module with an ASCII Terminal

Configure the interface module with an ASCII terminal only when the JW4 jumper
is in Configuration mode. Place the module in the Configuration mode that
corresponds to the functionality you chose for the interface module, as shown
below.

Refer to page 7 for location of jumper JW4.

Figure 5 JW4 Jumper Set for Configuration Mode

Configure the Module via the Backplane

Read and write configuration data through the backplane with series B interface
modules, and then only when the JW4 jumper is in the vertical Run mode position.
Place the module in vertical Run mode as shown below.

Refer to page 7 for location of jumper JW4.

Figure 6 JW4 Jumper Set for Vertical Run Mode

IMPORTANT

You can only use backplane communications if you selected
series B functionality for the module.

Horizontal Configuration

Mode

Vertical Configuration

Mode

Series A Functionality

Series B Functionality

JW4

Vertical Run Mode