Interpret the status indicators – Rockwell Automation 1734-AENTR POINT I/O 2 Port EtherNet/IP Adapter User Manual
Page 17

POINT I/O 2 Port Ethernet Adapter 17
Publication
1734-IN040B-EN-P - December 2009
Interpret the Status Indicators
Indicator
State
Description
Module
status
Off
No power applied to device
Solid green
Device operating normally
Flashing
red/green
Module self-test
Flashing red
Recoverable fault.
Complete firmware update, verify address switches.
Solid red
Unrecoverable fault, may require device replacement
Network
status
Off
Device is not on-line
- Device has not completed dup_MAC_id test.
- Device not powered - check module status indicator
Flashing green
Device is on-line but has no CIP connections in the
established state.
Solid green
Device on-line and has CIP connections in the established
state.
Flashing red
One or more CIP connections in timed-out state.
Check for I/O module failure and controller operation.
Solid red
Duplicate IP address detected.
Verify IP address setting and correct, as needed.
Flashing
red/green
Module self-test