Rockwell Automation 1734-AENTR POINT I/O 2 Port EtherNet/IP Adapter User Manual
Page 22

22 POINT I/O 2 Port Ethernet Adapter
Publication
1734-IN040B-EN-P - December 2009
General
Attribute
Value
Indicators
3 red/green status indicators on CPU:
- Module status
- Network status (Ports 1 and 2 combined)
- PointBus status
1 green/yellow status indicator on CPU:
- Network activity (Ports 1 and 2 combined)
2 green/yellow status indicators on base:
- Link 1 activity/status
- Link 2 activity/status
2 green power supply status indicators on DC-DC Converter:
- System power (5V DC to PointBus Out)
- Field power (24V DC from Field In)
Power consumption
10.4 W max @ 28.8V DC
Power dissipation
6.3 W max @ 28.8V DC
Input overvoltage protection
Reverse polarity protected
Thermal dissipation
21.5 BTU/hr max @ 28.8V DC
Isolation voltage
50V (continuous), Basic Insulation Type, Network to Power,
Network to Backplane, Power to Backplane, and Network to
Network.
Type tested at 1930V DC for 60 s
Field power supply
10…28.8V DC, 10A max
Field power output
10…28.8V DC, 9A max
Module input
10…28.8V DC, 1000 mA
PointBus output
5V DC, 0.8A max
Dimensions (HxWxD),
approx.
76.2 x 73.0 x 133.4 mm (3.0 x 2.87 x 5.25 in.)
Enclosure type rating
None (open-style)
Terminal base screw torque
0.8 Nm (7 lb-in)