Rockwell Automation 1734-AENTR POINT I/O 2 Port EtherNet/IP Adapter User Manual
Page 19

POINT I/O 2 Port Ethernet Adapter 19
Publication
1734-IN040B-EN-P - December 2009
POINTBus
status
Off
Device is not online.
Device has not completed Dup_MAC_ID test.
Device not powered - check module status indicator.
Flashing green
Device is online but has no connections in the established
state.
Firmware (NVS) update in progress.
Solid green
Adapter online with connections established.
Flashing red
Recoverable fault occurred:
• At cycle power, the number of expected modules
does not equal the number of modules present.
• A module is missing.
• Node fault (I/O connection timeout) occurred.
Solid red
Unrecoverable fault occurred - the adapter is bus off.
Flashing
red/green
LED powerup test is in progress.
System
power
Off
Not active. Adapter power is off or there is a DC-DC
converter problem.
Solid green
System power is on. DC-DC converter output is active (5V).
Field power Off
Not active. Adapter power is off.
Solid green
Power is on. 24V input is present.
Indicator
State
Description