Ground the Power Supply

Ground the power supply on a ground bus with a dedicated earth-ground stake.
The ground bus should also be connected to a functional earth ground on the DIN
rail or panel. The upper left tab on the power supply serves as a functional ground.

Refer to Industrial Automation Wiring and Grounding Guidelines, Allen-Bradley
publication 1770-4.1, for additional information.

Wire the Ground

Complete the following steps to wire the protective-earth ground:

1. Locate the protective-earth ground terminal, indicated by the following

symbol.

2. Turn the screw counterclockwise to open the terminal.

ATTENTION

This product is grounded through the DIN rail to chassis ground. Use
zinc-plated yellow-chromate steel DIN rail to assure proper grounding. The
use of other DIN rail materials, for example, aluminum or plastic, that can
corrode, oxidize, or are poor conductors, can result in improper or intermittent
grounding. Secure DIN rail to mounting surface approximately every 200 mm
(7.87 in.) and use end-anchors appropriately.