28 1768 CompactLogix Power Supplies

Publication 1768-IN001B-EN-P - July 2006

Output #1: 24V dc to Backplane

Ride-through
Interval Time, Min

25 ms @ 90 W

5 ms @ 90 W

Full Power Hold-up
Interval

5 ms @ 90 W

Extended Hold-up
Interval

8…12 s @ 1.25 W

Output #2: 24V dc to Front Panel Terminal Block

Voltage

18…27.60V @ front panel

Output Disable

Disable output during hold-up periods

(1)

Use this Conductor Category information when planning conductor routing. Refer to Industrial Automation Wiring and
Grounding Guidelines, publication 1770-4.1.

(2)

Does not include X-capacitor charging current.

Environmental Specifications

Attribute

1768-PA3

1768-PB3

Conducted RF Immunity

IEC 61000-4-6
10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

EFT/B Immunity

IEC 61000-4-4:
±4kV at 5 kHz on power ports

Emissions

CISPR 11:
Group 1, Class A

ESD Immunity

IEC 61000-4-2:
6 kV contact discharges
8 kV air discharges

Radiated RF Immunity

IEC 61000-4-3:

• 10V/m with 1 kHz sine-wave 80%AM from 30…2000 MHz
• 10V/m with 200 Hz 50% Pulse 100%AM at 900 MHz
• 10V/m with 200 Hz 50% Pulse 100%AM at 1890 MHz
• 1V/m with 1 kHz sine-wave 80%AM from 2000…2700 MHz

Relative Humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…95% noncondensing

Shock, Operating

IEC 60068-2-27 (Test Ea, Unpackaged Shock):
30 g

Shock, Nonoperating

IEC 60068-2-27 (Test Ea, Unpackaged Shock):
50 g

1768-PA3 and 1768-PB3, CompactLogix Power Supplies

Attribute

1768-PA3

1768-PB3