1768 CompactLogix Power Supplies 29

Publication 1768-IN001B-EN-P - July 2006

Surge Transient Immunity

IEC 61000-4-5:

• ±2 kV line-line (DM) and ±4 kV

line-earth (CM) on ac power
ports

• ±1 kV line-line (DM) and ±2 kV

line-earth (CM) on dc power
ports

IEC 61000-4-5:

±1 kV line-line (DM) and ±2 kV
line-earth (CM) on dc power ports

Temperature, Operating

IEC 60068-2-1 (Test Ad, Operating Cold)

IEC 60068-2-2 (Test Bd, Operating Dry Heat)

IEC 60068-2-14 (Test Nb, Operating Thermal Shock):

0…60 °C (32…140 °F)

Temperature, Storage

IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold)
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat)
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock):

-40…85 °C (-40…185 °F)

Vibration

IEC 60068-2-6 (Test Fc, Operating):
5 g @ 10…500 Hz

Voltage Variation

IEC 61000-4-11:

• 30% dips for 1 period at 0° &

180° on ac supply ports

• 60% dips for 5 & 50 periods

on ac supply ports

• ±10% fluctuations for 15 min

on ac supply ports

• > 95% interruptions for 250

periods on ac supply ports

IEC 61000-4-29:

• 60% dip for 100 ms on dc

supply ports

• 30% dip for 10 ms on dc

supply ports

• 100% dip for 10 ms on dc

supply ports

• ±20% fluctuations for 15 min

on dc supply ports

• 5 s interruptions on dc supply

ports

Environmental Specifications

Attribute

1768-PA3