If the
controller PWR
status
indicator is

It means

Take this action

Off

Either the controller
or the power supply is
not operating
properly. Most likely,
in this case, the
controller has an
issue because the
power supply PWR
status indicator is
green.

Green

The controller is
operating properly
with respect to
sending power to the
1768 modules.

Check the controller I/O PWR status indicator to make sure the
entire system is operating properly.

Red

One of the following:

1768 CompactLogix Power Supplies 25

Publication 1768-IN001B-EN-P - July 2006

A. Make sure all modules in the system are installed properly

and fully engaged with each other.

B. If the controller PWR status indicator remains off, move to

the next step.

C. Remove any 1768 communication or motion modules.

D. Reinstall the controller directly next to the power supply and

reapply power.

E. If the controller PWR status indicator remains off, replace

the controller.

F. If the controller PWR status indicator on the new controller

remains off, replace the power supply.

• The controller

needs to be
replaced.

• If 1768

communication
and motion
modules are
installed in the
system, one of
the 1768 modules
needs to be
replaced.

A. Disconnect all of the 1768 communication and motion

modules from the system.

B. Reapply power.

C. Check the controller PWR status indicator.

• If the status indicator is green, the controller is operating

properly and one of the other 1768 modules needs to be
replaced.

• To troubleshoot the 1768 modules, see their respective

installation instructions. For a list of related publications,
see Additional Resources.

• If the status indicator remains red, replace the controller.