FLEX I/O Isolated Input HART Analog Module 13
Publication
1794-IN115C-EN-P - April 2009
Input Map
Word
Bit
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
0
Channel 0 Input Data
1
Channel 1 Input Data
2
Channel 2 Input Data
3
Channel 3 Input Data
4
Channel 4 Input Data
5
Channel 5 Input Data
6
Channel 6 Input Data
7
Channel 7 Input Data
8
H
7
H
6
H
5
H
4
H
3
H
2
H
1
H
0
L
7
L
6
L
5
L
4
L
3
L
2
L
1
L
0
9
R
7
R
6
R
5
R
4
R
3
R
2
R
1
R
0
P
7
P
6
P
5
P
4
P
3
P
2
P
1
P
0
10
Reserved
Diagnostic Status
11
C
7
C
6
C
5
C
4
C
3
C
2
C
1
C
0
F
7
F
6
F
5
F
4
F
3
F
2
F
1
F
0
12
X
7
X
6
X
5
X
4
X
3
X
2
X
1
X
0
Reserved
Hn:
Ln:
Pn:
Rn:
Fn:
Cn:
Xn:
Channel n High Alarm
Channel n Low Alarm
Channel n Out Of Range Alarm
Channel n Second (Remote) Alarm
Channel n HART Failure
Channel n HART Current Fault
Channel n HART Transmitter Present
0: False 1: True
0: False 1: True
0: False 1: True
0: False 1: True
0: False 1: True
0: False 1: True
0: False 1: True
Note: Reserved data may not be shown in certain controller software