Cyclic HART Input Data

The HART input data holds the primary variables for the "live" HART
device, and other information gathered during the normal HART
scan. Additional "documentary" data is available through the pass
through message interface in the device information tables. Pass
through messages are defined in detail in the User Manual.

Format Values

Format Format name

0.0 mA

2.0 mA

4.0 mA

20.0 mA

22.0 mA

0

0…20 mA in
Milliamps

0

2000

4000

20000

22000

1

0…20 mA in % Full
Scale

0

1000

2000

10000

11000

3

0…20 mA in UINT

0

6554

13107

65535

65535

(1)

4

4…20 mA in
Milliamps

2000

(1)

2000

4000

20000

22000

5

4…20 mA in % Full
Scale

1000

(1)

1000

2000

10000

11000

7

4…20 mA in UINT

0

(1)

0

(1)

0

65535

65535

(1)

(1)

These values are under, or over the supported user range, and are clamped at the lowest/highest
supported values.

IMPORTANT

The HART Input Data for a channel may be zeroes if HART communications
is disabled for that channel. For more information on disabling HART
communications, refer to the Disable HART communications and HART
CMD 3 Disable functions in the Configuration Map table.