Rockwell Automation 1794-IF8IH FLEX I/O 8 Isolated Input HART Analog Module Installation Instructions User Manual
Page 16
![background image](/manuals/579567/16/background.png)
16 FLEX I/O Isolated Input HART Analog Module
Publication
1794-IN115C-EN-P - April 2009
Cn
HART CMD 3 Disable
0: HART CMD 3
communications
enabled
1: HART CMD 3
communications
disabled
R
Reserved
CH N Format
Refer to the Channel Data Formats table
Byte Order
Byte Order
Group B
Byte Order
Group A
Bit 9
Bit 8
Bit 1
Bit 0
Description
0
0
0
0
Little Endian Format (default) — all data entries in true
Little Endian format
1
0
1
0
Word Swap — word swap only values requiring more
than one word, for example, 32 bit float values.
0
1
0
1
Byte Swap — byte swap all words in data table.
1
1
1
1
Big Endian Format — all data entries in true Big Endian
format.
Channel Digital Filter
Digital Filter
frequency
Decimal Value
Bits
10
9
8
2
1
0
470 Hz
0
0
0
0
62 Hz
1
0
0
1
19.6 Hz
2
0
1
0
16.7 Hz
3
0
1
1
10 Hz
4
1
0
0
Configuration Map descriptions