Rockwell Automation 1794-IF8IH FLEX I/O 8 Isolated Input HART Analog Module Installation Instructions User Manual

Page 16

Advertising
background image

16 FLEX I/O Isolated Input HART Analog Module

Publication

1794-IN115C-EN-P - April 2009

Cn

HART CMD 3 Disable

0: HART CMD 3
communications
enabled

1: HART CMD 3
communications
disabled

R

Reserved

CH N Format

Refer to the Channel Data Formats table

Byte Order

Byte Order
Group B

Byte Order
Group A

Bit 9

Bit 8

Bit 1

Bit 0

Description

0

0

0

0

Little Endian Format (default) — all data entries in true
Little Endian format

1

0

1

0

Word Swap — word swap only values requiring more
than one word, for example, 32 bit float values.

0

1

0

1

Byte Swap — byte swap all words in data table.

1

1

1

1

Big Endian Format — all data entries in true Big Endian
format.

Channel Digital Filter

Digital Filter
frequency

Decimal Value

Bits

10

9

8

2

1

0

470 Hz

0

0

0

0

62 Hz

1

0

0

1

19.6 Hz

2

0

1

0

16.7 Hz

3

0

1

1

10 Hz

4

1

0

0

Configuration Map descriptions

Advertising