Connecting to the rs-232 port, Connecting to the rs-232 port -3, Program compare -4 – Rockwell Automation 1764-xxxx MICROLOGIX 1500 PROGRAMMABLE CONTROLLERS User Manual
Page 71: Df1 full-duplex communication parameters, Making a df1 full-duplex point-to-point connection

Publication 1764-UM001B-EN-P - April 2002
Communication Connections 4-3
Connecting to the RS-232
Port
DF1 Full-Duplex Communication Parameters
When a communication channel is configured for DF1 Full-Duplex,
the following parameters can be changed.
Making a DF1 Full-Duplex Point-to-Point Connection
You can connect the MicroLogix 1500 programmable controller to
your personal computer using a serial cable from your personal
computer’s serial port to the controller, as shown in the illustrations
below.
Table 4.2 DF1 Full-Duplex Configuration Parameters
Parameter
Options
Default
Baud Rate
300, 600, 1200, 2400, 4800, 9600, 19.2K, 38.4K 19.2K
Parity
none, even
none
Source ID (Node
Address)
0 to 254 decimal
1
Control Line
no handshaking, Full-Duplex modem
handshaking
no
handshaking
Error Detection
CRC, BCC
CRC
Embedded Responses
auto-detect, enabled
auto detect
Duplicate Packet
(Message) Detect
enabled, disabled
enabled
ACK Timeout
1 to 65535 counts (20 ms increments)
50 counts
NAK retries
0 to 255
3 retries
ENQ retries
0 to 255
3 retries
Stop Bits
not a setting, always 1
1
ATTENTION
!
Chassis ground, internal 24V ground, user 24V dc
ground, and RS-232 ground are internally connected.
You must connect the chassis ground terminal screw
to ground prior to connecting any devices. It is
important that you understand your personal
computer’s grounding system before connecting to
the controller. An optical isolator, such as the
1761-NET-AIC, is recommended between the
controller and your personal computer when using
Channel 0. An isolator is not required when using
Channel 1 (1764-LRP).