Rockwell Automation 1764-xxxx MICROLOGIX 1500 PROGRAMMABLE CONTROLLERS User Manual
Page 85

Publication 1764-UM001B-EN-P - April 2002
Communication Connections 4-17
1761-CBL-AC00
1747-CP3
Cable
Length
Connections from
to AIC+
External Power
Supply Required
(1)
Power Selection
Switch Setting
1747-CP3
1761-CBL-AC00
3m (9.8 ft)
45cm (17.7 in)
1764-LRP processor, channel 1
port 1
yes
external
SLC 5/03 or SLC 5/04 processor, channel 0
port 1
yes
external
PC COM port
port 1
yes
external
PanelView 550 through NULL modem adapter port 1
yes
external
DTAM Plus / DTAM Micro™
port 1
yes
external
Port 1 on another AIC+
port 1
yes
external
(1) External power supply required unless the AIC+ is powered by the device connected to port 2, then the selection switch should be set to
cable.
user supplied cable
Cable
Length
Connections from
to
AIC+
External Power
Supply Required
(1)
Power Selection
Switch Setting
straight
9-25 pin
—
modem or other communication device
port 1
yes
external
(1) External power supply required unless the AIC+ is powered by the device connected to port 2, then the selection switch should be set to
cable.
1761-CBL-AS03
1761-CBL-AS09
Cable
Length
Connections from
to AIC+
External Power
Supply
Required
(1)
Power
Selection
Switch
Setting
1761-CBL-AS03
1761-CBL-AS09
3m (9.8 ft)
9.5m (31.17 ft)
SLC 500 Fixed,
SLC 5/01, SLC 5/02, and SLC 5/03 processors
port 3
yes
external
PanelView 550 RJ45 port
port 3
yes
external
(1) External power supply required unless the AIC+ is powered by the device connected to port 2, then the selection switch should be set to
cable.