Chapter 3 – Rockwell Automation 1785-L20C_L40C, D17856.5.14 ControlNet PLC-5 Programmable Controllers User Manual User Manual
Page 55

Chapter 3
Configuring Your ControlNet System
3-11
Do this:
If you want to:
change a module's idle action
Ċi.e., the action that it takes
when it becomes idle
1. Move the cursor to the module's
Idle
Action
field
2. Press
[F10]—Toggle
Entry
to toggle between:
•
Reset
Ċto change all outputs to zero
•
Hold
Last
Ċto maintain all current output values
•
Safe
Ċto change all outputs to userĆspecified fail-safe values
change a module's fault action
from idleĊi.e., the action that
it takes when it faults from idle
1. Move the cursor to the module's
Fault
Action
From
Idle
field
2. Press
[F10]—Toggle
Entry
to toggle between:
•
Idle
Ċto use the idle action
•
Fault
Ċto use the fault action
apply pending edits and return
to the ControlNet I/O Mapping
(Edit) screen
Press
[F1]—Accept
Edits
go back to the ControlNet I/O
Mapping (Edit) screen
Press
[F2]—Map
Edit
or
[Esc]