1769-L20, 1769-L30 CompactLogix™ Controllers 13

Publication 1769-IN047C-EN-P - April 2003

RS-232 Connections to the Controller

The following illustrations show which cables can be used to connect to the
controller. To connect two cables to the 1769-L30 controller, you must connect the
straight cable end to Channel 0.

ATTENTION

!

When you connect or disconnect the serial cable while
backplane power is on, an electrical arc can occur. In
hazardous locations, this could cause an explosion.

NOTE: The Channel 0 port is locally
grounded. Only Channel 1 of the 1769-L30
controller is electrically isolated.

1769-L20 controller

1769-L30 controller

2 RDX

3 TXD

4 DTR

COMMON

6 DSR

7 RTS

8 CTS

9

1 CD

2 RDX

3 TXD

4 DTR

COMMON

6 DSR

7 RTS

8 CTS

9

1 CD

1747-CP3 or 1756-CP3

9-pin, male D-shell straight
cable end

9-pin, female D-shell
right-angle cable end

straight cable end

right-angle cable end

This cable must be shielded and tied to the connector
housing.