16 1769-L20, 1769-L30 CompactLogix™ Controllers

Publication 1769-IN047C-EN-P - April 2003

Troubleshoot the Controller Using the LEDs

Indicator

Color/Status

Description

RUN

Off

No task(s) running

Controller in Program mode

Green

One or more tasks are running

Controller is in the Run mode

FORCE

Off

No forces enabled

Amber

Forces enabled

Amber Flashing

One or more input or output addresses have been forced to an On
or Off state, but the forces have not been enabled

BAT

Off

Battery supports memory

Red

Battery may not support memory, replace battery

OK

Off

No power applied

Green

Controller OK

Red flashing

Recoverable controller fault

Red

Non-recoverable controller fault:
Cycle power. The OK LED should change to flashing red.

If LED remains solid red, replace the controller.

I/O

Off

(1)

(1)

If the controller does not contain an application (controller memory is empty), the I/O indicator will be off.

No activity

No I/O or communications configured

Green

Communicating to all modules

Green flashing

One or more modules not responding

Red flashing

Not communicating to any modules

DCH0

Off

User-configured communications active

Green

Default communication configuration active

Channel 0

Off

No activity

Green

Network activity (DH485)

Green flickering

Data is being received or transmitted (DF1)

Channel 1

Off

No activity

Green

Network activity (DH485)

Green flickering

Data is being received or transmitted (DF1)