14 1769-L20, 1769-L30 CompactLogix™ Controllers

Publication 1769-IN047C-EN-P - April 2003

Default Communication Configuration

Channel 0 and Channel 1 (1769-L30 controller only) have the following default
communication configuration.

Parameter

Default

Protocol

DF1 full-duplex

Baud Rate

19.2K

Parity

none

Station Address

0

Control Lines

no handshaking

Error Detection

BCC

Embedded Responses

auto detect

Duplicate Packet (Message) Detect

enabled

ACK Timeout

50 (x 20 ms)

NAK Receive Limit

3 retries

ENQ Transmit Limit

3 retries

Data Bits

8

Stop Bits

1