6 1769-L20, 1769-L30 CompactLogix™ Controllers

Publication 1769-IN047C-EN-P - April 2003

CompactLogix Controller Description

System Planning

Consider the following when planning your CompactLogix system:

· The CompactLogix controller is always the left-most module in the system.
· The controller must be located within four modules of the system power

supply. Some I/O module’s may be located up to 8 modules away from the
power supply. See the documentation for your 1769 I/O modules for details.

· The 1769-L20 controller supports up to 8 I/O modules in a maximum of 2

I/O banks (1 expansion cable allowed).

· The 1769-L30 controller supports up to 16 I/O modules in a maximum of 3

I/O banks (2 expansion cables allowed).

· Each I/O bank requires its own power supply.
· Only one controller can be used in a CompactLogix system.
· A 1769-ECR (right end cap) or 1769-ECL (left end cap) is required to

terminate the end of the communication bus.

1

DIN rail latch

8

Channel 0 RS-232 Port

2

panel mounting tab

9

Channel 0 default communication push button

3

tongue and groove slots

10

Channel 1 RS-232 Port

4

stationary bus connector

11

Channel 1 RS-232 Port Status LED

5

status LEDs

12

battery door

6

key switch

13

battery door label

7

Channel 0 RS-232 Port Status LED

14

battery

(1)

(1)

See Connect the Battery on page 8 for the actual position of the battery.

15

battery connector

1

1

2

2

3

3

4

5

6

7

8

7

8

9

9

10

14

15

12

13

11

1769-L20 controller

1769-L30 controller