Ground the module, Output wiring – Rockwell Automation 1762-OF4 MicroLogix Analog Output Module User Manual

Page 12

Advertising
background image

12 Analog Output Module

Publication 1762-IN016D-EN-P - June 2013

Output Wiring

Basic wiring of input devices to the 1762-OF4 is shown below.

Terminal Block Layout

Differential Sensor Transmitter Types

Ground the Module

This product is intended to be mounted to a well-grounded mounting surface such as a metal
panel. Additional grounding connections from the module’s mounting tabs or DIN rail (if used)
are not required unless the mounting surface cannot be grounded. Refer to Industrial
Automation Wiring and Grounding Guidelines, Allen-Bradley publication

1770-4.1

, for

additional information.

TIP

Grounding the cable shield at the module end only usually provides sufficient
noise immunity. However, for best cable shield performance, earth ground the
shield at both ends, using a 0.01 µF capacitor at one end to block AC power
ground currents, if necessary.

V out 3

V out 2

V out 1

V out 0

I out 3

I out 2

I out 1

I out 0

COM

COM

Commons connected
internally.

I out 0

I out 1

V out 2

V out 3

V out 0

V out 1

COM

I out 3

I out 2

COM

Current Load

Voltage Load