16 Analog Output Module

Publication 1762-IN016D-EN-P - June 2013

Configuration Data File

The configuration of the format for analog outputs is made at going to run (GTR). Changes
made to the configuration file while in run mode have no effect on the outputs.

The configuration table for analog outputs is shown in the Configuration Data File table.

Bit 15 and Bits 7…0 - Reserved

These bits are reserved and are not checked by the module.

Data Format (Bits 14…12)

These bits indicate the format of the data as shown in the following table. Other combinations of
these bits are not supported and result in an error.

Configuration Data File

Wo

rd

Bit Position

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

0

re

se

rv

ed

Data Format
Output Channel 0

Type/Range Select
Output Channel 0

reserved

1

Data Format
Output Channel 1

Type/Range Select
Output Channel 1

reserved

2

Data Format
Output Channel 2

Type/Range Select
Output Channel 2

reserved

3

Data Format
Output Channel 3

Type/Range Select
Output Channel 3

reserved

4

reserved

5

reserved

6

reserved

7

reserved

Bit Settings

Data Format

14

13

12

0

0

0

Raw/Proportional

0

1

0

Scaled for PID

other

Not Supported