Configuration data file – Rockwell Automation 1762-OF4 MicroLogix Analog Output Module User Manual
Page 16

16 Analog Output Module
Publication 1762-IN016D-EN-P - June 2013
Configuration Data File
The configuration of the format for analog outputs is made at going to run (GTR). Changes
made to the configuration file while in run mode have no effect on the outputs.
The configuration table for analog outputs is shown in the Configuration Data File table.
Bit 15 and Bits 7…0 - Reserved
These bits are reserved and are not checked by the module.
Data Format (Bits 14…12)
These bits indicate the format of the data as shown in the following table. Other combinations of
these bits are not supported and result in an error.
Configuration Data File
Wo
rd
Bit Position
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
0
re
se
rv
ed
Data Format
Output Channel 0
Type/Range Select
Output Channel 0
reserved
1
Data Format
Output Channel 1
Type/Range Select
Output Channel 1
reserved
2
Data Format
Output Channel 2
Type/Range Select
Output Channel 2
reserved
3
Data Format
Output Channel 3
Type/Range Select
Output Channel 3
reserved
4
reserved
5
reserved
6
reserved
7
reserved
Bit Settings
Data Format
14
13
12
0
0
0
Raw/Proportional
0
1
0
Scaled for PID
other
Not Supported