General – Rockwell Automation 1762-OF4 MicroLogix Analog Output Module User Manual

Page 19

Advertising
background image

Analog Output Module 19

Publication 1762-IN016D-EN-P - June 2013

General

Attribute

Value

Dimensions, HxWxD

90 x 40.4 x 87 mm
(3.54 x 1.59 x 3.43 in.)

Approximate shipping weight
(with carton)

235 g (8.28 oz)

Bus current draw, max

40 mA @ 5V DC
165 mA @ 24V DC

Analog normal operating range

Voltage: 0…10V DC
Current: 4…20 mA

Full scale

(1)

analog ranges

(1)

The over- or under-range flag comes on when the normal operating range (over/under) is exceeded. The module continues
to convert the analog output up to the maximum full scale range.

Voltage: 0…10.5V DC
Current: 0…21 mA

Resolution

12 bits (unipolar)

Repeatability

(2)

(2)

Repeatability is the ability of the output module to reproduce output reading when the same controller value is applied to it
consecutively, under the same conditions and in the same direction.

±0.12%

Output group to system isolation

30V AC/30V DC rated working voltage

(4)

(IEC Class 2 reinforced insulation)
type test: 500V AC or 707V DC for 1 minute

(4)

Rated working voltage is the maximum continuous voltage that can be applied at the terminals with respect to earth
ground.

Module power LED

On: indicates power is applied.

Recommended cable

Belden 8761 (shielded)

Heat Dissipation

2.8 W

Wiring category

(3)

(3)

Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and
Grounding Guidelines, publication

1770-4.1

.

2 - on signal ports

Pilot duty rating

Not rated

Enclosure type rating

IP20

North American temp code

T3C

Vendor ID code

1

Product type code

10

Product code

66

Advertising