Input data file, O0:x.0/0, Labeling the terminals – Rockwell Automation 1762-OF4 MicroLogix Analog Output Module User Manual

Page 14: 1762 expansion i/o addressing

Advertising
background image

14 Analog Output Module

Publication 1762-IN016D-EN-P - June 2013

Labeling the Terminals

A write-on label is provided with the module. Mark the identification of each terminal with
permanent ink, and slide the label back into the door.

1762 Expansion I/O Addressing

The addressing scheme for 1762 Expansion I/O is represented in the following figure.

Input Data File

For each module, slot x, words 0 and 1 contain the analog output module status data for use in
the control program.

The bits are defined as follows:

• SOx = General status bits for output channels 0…3. This bit is set when an error (over- or

under-range) exists for that channel, or there is a general module hardware error.

• OOx = Over-range flag bits for output channels 0…3. These bits indicate an input signal

above the user range and can be used in the control program for error detection. The
module continues to convert analog data to the maximum full range value while this bit
is set (1). The bit is reset (0) when the error clears.

Wo

rd

Bit Position

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

0

Reserved

SO3

SO2

SO1

SO0

1

Reserved

UO0

OO0

UO1

OO1

UO2

OO2

UO3

OO3

O0:x.0/0

Slot number

(1)

Output Data file (0)

Output

Slot delimiter

Word delimiter

Bit delimiter

Bit (0...15)

Word

(1)

I/O located on the controller (embedded I/O) is slot 0. I/O added to the controller (expansion I/O) begins with slot 1.