Troubleshoot the Module

If the lights on the module
look like this

Then do this

CP

Ring

OK

Off

Off

Off

• Make sure the module is connected and locked to the

other modules.

• Check the power supply and controller to make sure

the backplane has power.

Off

Off

Flashing
Red

Wait! Someone is updating the firmware of the module.

Flashing
Orange

Off

Flashing
Green

• Look for cables that are broken, unplugged, or in the

wrong port.

• Check the drives for faults.

Solid
Orange

Flashing
Red

Flashing
Green

• Make sure each drive has its own address.
• Make sure that all of the drives have the same baud

rate.

• Set the Data Rate of the SERCOS interface module to

Auto-Detect.

• Check the Cycle Time of the SERCOS interface

module. See Specifications on page 23.

Flashing
Red and
Green

Flashing
Green

Flashing
Green

Did you configure the module?

• NO — Use RSLogix 5000 software to configure the

module.

• YES — Check the configuration of the module and

drives in RSLogix 5000 software.

SERCOS Phase

SERCOS Ring Status

Module Status