Alphanumeric display codes – Rockwell Automation 1756-DHRIOXT ControlLogix-XT Data Highway Plus-Remote I/O Communication Interface Module User Manual

Page 21

Advertising
background image

ControlLogix-XT Data Highway Plus-Remote I/O Interface Module 21

Publication

1756-IN638A-EN-P - March 2009

Alphanumeric Display Codes

Your 1756-DHRIOXT module displays alphanumeric codes that
provide diagnostic information. The alphanumeric display flashes the
codes at approximately 1-second intervals. These tables describe
codes and interpretations specific to the application of the module.

Data Highway Plus Codes and Interpretations

Code

Description

Recommended Action

OFF

LINE

Data Highway Plus link is in
STOP state.

Correct the configuration. Refer to the
1756-DHRIO User Manual, publication

1756-UM514

.

DUPL

NODE

Data Highway Plus Duplicate
node address.

Choose another node address and reset
switches.

ONLY

NODE

Only node on Data Highway
Plus link.

Check the cables.

CNFG

FALT

Incorrect DH+ routing table
configuration.

Incorrect Data Highway
object configuration.

Correct the configuration. Refer to the

1756-DHRIO User Manual, publication

1756-UM0514

.

Verify that the module is inserted in

the correct slot.

OK

Normal operation for that
channel.

None.

LINK

OFF

Channel B is disabled
because Channel A is used
for 230k DH+ operation.

None.