24 ControlLogix-XT Data Highway Plus-Remote I/O Interface Module

Publication

1756-IN638A-EN-P - March 2009

Status Indicators

Three status indicators on the module provide information about
your module and the status of each channel. The following tables
outline the indicator condition and the corresponding status, and
explain what each condition means.

OK Status Indicator

State

Description

Recommended Actions

Off

The module is not
operating.

Apply chassis power.

Verify module is completely

inserted into chassis and
backplane.

Flashing green

The module is
operational, but either:

is not routing

messages

the controller is not

transferring I/O.

None if no messages are actively
being routed through the module and
no controller transferring I/O.

To route messages or transfer I/O, use
module default configuration or
configure module.

Green

Operational and is
routing messages.

None - this is normal operation.

Red, then off

Performing a self-test.

None - this is normal operation.

Red

In major fault

Reboot module. If red reoccurs, then

replace module.

Flashing red

In major fault or
configuration fault.

Check alphanumeric indicator and
take action described in alphanumeric
display message table on page 21.