General specifications - 1756-dhrioxt – Rockwell Automation 1756-DHRIOXT ControlLogix-XT Data Highway Plus-Remote I/O Communication Interface Module User Manual

Page 26

Advertising
background image

26 ControlLogix-XT Data Highway Plus-Remote I/O Interface Module

Publication

1756-IN638A-EN-P - March 2009

General Specifications - 1756-DHRIOXT

Attribute

Value

Module location

1756 ControlLogix-XT chassis, any slot

Backplane current

(mA) at 24V

1.7 mA

Backplane current

(mA) at 5V

850 mA

Power dissipation, max

4.5 W

Thermal dissipation, max

15.4 BTU/hr

Baud rate

57.6 Kbaud

115.2 Kbaud

230.4 Kbaud

Isolation voltage

30V (continuous), Basic Insulation Type

Type tested at 853V AC for 60 s, DHRIO to system and
DHRIO port to DHRIO port.

North American temp code

T4A

IEC temp code

T4

Enclosure type rating

None (open-style)

Wire size

0.2...2.0 mm

2

(24...14 AWG)

Copper twinaxial; Belden 9463 recommended.

Wiring category

2 - on communications ports

(1)

(1)

Use this conductor category information for planning conductor routing as described in system level
installation manual. Also refer to Industrial Automation Wiring and Grounding Guidelines,
publication

1770-4.1

.