Rockwell Automation 1771-IBN DC (10-30V) INPUT Module Installation Instructions User Manual

Page 17

Advertising
background image

DC (10...30V) Input Module 17

Publication 1771-IN028D-EN-P - October 2008

Environmental Specifications

Attribute

Value

Temperature, operating

IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
0…60 °C (32…140 °F)

Temperature, nonoperating

IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-40…85 °C (-40…185 °F)

Vibration

IEC 60068-2-6 (Test Fc, Operating):
2 g @ 10…500 Hz

Relative humidity

IEC 60068-2-30 (Test Db, Unpackaged Damp Heat):
5…95% noncondensing

Shock, operating

IEC 60068-2-27 (Test Ea, Unpackaged Shock): 30 g

Shock, nonoperating

IEC 60068-2-27 (Test Ea, Unpackaged Shock): 50 g

ESD immunity

IEC 61000-4-2:
4 kV indirect contact discharges

Radiated RF immunity

IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80% AM from
80…2000 MHz
1V/m with 1 kHz sine-wave 80% AM from
2000…2700 MHz

EFT/B immunity

IEC 61000-4-4:
±1 kV at 5 kHz on signal ports

Surge transient immunity

IEC 61000-4-5:
±1 kV line-line (DM) and ±2 kV line-earth (CM) on
signal ports

Conducted RF immunity

IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM
from 150 kHz…80 MHz

Emissions

CISPR 11:
Group 1, Class A (with appropriate enclosure)