4 DC (10...30V) Input Module

Publication 1771-IN028D-EN-P - October 2008

European Hazardous Location Approval

ATTENTION

This equipment is intended for use in potentially explosive atmospheres as defined by
European Union Directive 94/9/EC and has been found to comply with the Essential
Health and Safety Requirements relating to the design and construction of Category 3
equipment intended for use in potentially explosive atmospheres, given in Annex II to this
Directive.

Compliance with the Essential Health and Safety Requirements has been assured by
compliance with EN 60079-15 and EN 60079-0.

WARNING

Observe the following additional Zone 2 certification requirements:

• This equipment is not resistant to sunlight or other sources of UV radiation.
• This equipment must be installed in an enclosure providing at least IP54 protection

when applied in Zone 2 environments.

• This equipment shall be used within its specified ratings defined by Allen-Bradley.
• Provision shall be made to prevent the rated voltage from being exceeded by

transient disturbances of more than 40% when applied in Zone 2 environments.

• This equipment must be used only with ATEX certified backplanes.
• Secure any external connections that mate to this equipment by using screws, sliding

latches, threaded connectors, or other means provided with this product.

• Do not disconnect equipment unless power has been removed or the area is known to

be nonhazardous.