Use bootp to set the ip address, Use switches to set the ip address, Add a 1788-en2par module in rslogix 5000 software – Rockwell Automation 1788-EN2PAR Redundant EtherNet/IP to PROFIBUS PA Linking Device Quick Start User Manual

Page 4: Bootp to set the ip address

Advertising
background image

4 Redundant EtherNet/IP to PROFIBUS PA Linking Device

Use BOOTP to Set the IP Address

1. Set the Ethernet switches to 888 (factory default).
2. Apply power to the linking device.
3. Set the IP address by using any BOOTP server.
4. Once the new IP address has been set, power down the linking device.
5. Return the switches to 000.
6. Apply power to the linking device.

Use Switches to Set the IP Address

To set the IP address of the linking device to the 192.168.1.xxx sub net, set the switches to the
required last three digits.

Add a 1788-EN2PAR Module in RSLogix 5000 Software

The module must be added to the RSLogix 5000 IO tree by selecting the 1788-EN2PAR
module (under an Allen-Bradley Ethernet bridge, such as EN2T).

1. Right-click the Ethernet bridge and choose New Module.

2. Expand the Hiprom Technologies option and select 1788-EN2PAR

The Module Properties dialog box appears.

3. Type the module’s Name, Description, IP Address, and RPI.
4. Click OK.