20 GuardPLC 1800 Controllers

Rockwell Automation Publication 1753-IN002C-EN-P - June 2010

Communication via GuardPLC Ethernet is indicated by two small status indicators integrated
into all connecting sockets.

Additional nonsafety-related communication occurs on the field buses and is indicated by the
status indicators.

Specifications

Indicator

State

Description

Green

On

Full-duplex operation

Flashing

Collision

Off

Half-duplex operation, no collision

Yellow

On

Connection established

Flashing

Interface activity

Indicator

Connection

Description

Green

COMM 1

RS-485 interface, field bus active

COMM 2

Unassigned

COMM 3

Unassigned

Technical Specifications – GuardPLC 1800 Controllers

Attribute

1753-L28BBBM-8A, 1753-L28BBBP-8A

User memory

250 KB max user program memory
250 KB max application data memory

Watchdog time, min

10 ms

Safety time, min

20 ms

Current consumption

9 A max (with max load)
0.75 A idle current

Operating voltage

24V DC, -15…20%, w

ss

15% (from a power supply with protective

separation conforming to IEC 61131-2 requirements)

Isolation voltage

50V (continuous), Basic Insulation Type, I/O to Ethernet and Ethernet to DC
power

Wiring category

(1)

Category 2 on communication ports, signal ports, and power ports

Wire size

I/O – 0.13…1.3 mm

2

(26…16 AWG) solid or stranded copper wire rated at

75 °C (167 °F) or greater with 1.2 mm (3/64 in.) insulation max

Power – 0.33…2.1 mm

2

(22…14 AWG) solid or stranded copper wire rated

at 75 °C (167 °F) or greater with 1.2 mm (3/64 in.) insulation max

Ethernet – RJ45 connector according to IEC 60603-7, 2 or 4-pair Category
5e minimum cable according to TIA 568-B.1, or Category 5 cable according
to ISO/IEC 24702

Comm: 9-pin D-sub