Digital input terminals – Rockwell Automation 1753-L32BBBP-8A GuardPLC 1800 Controller User Manual

Page 8

Advertising
background image

8 GuardPLC 1800 Controllers

Rockwell Automation Publication 1753-IN002C-EN-P - June 2010

The safe state of an input is indicated by a 0 signal being passed to the user program logic. If the
test routines detect a fault in the digital inputs, a 0 signal is processed in the user program for the
defective channel. When a fault occurs, the inputs are switched off (0).

Follow the closed-circuit principle for external wiring when connecting sensors. To create a safe
state in the event of a fault, the input signals revert to the de-energized state (0). The FAULT
status indicator activates.

Digital Input Terminals

Terminals accommodate wires up to 1.5 mm

2

(16 AWG). See the terminal torque specifications

on page

21

. Digital inputs are connected to these terminals.

Terminal Number

Designation

Function

11

LS+

Sensor supply for inputs 1…8

12

1

Digital input 1

13

2

Digital input 2

14

3

Digital input 3

15

4

Digital input 4

16

5

Digital input 5

17

6

Digital input 6

18

7

Digital input 7

19

8

Digital input 8

20

L-

Reference pole

21

LS+

Sensor supply for inputs 9…16

22

9

Digital input 9

23

10

Digital input 10

24

11

Digital input 11

25

12

Digital input 12

26

13

Digital input 13

27

14

Digital input 14

28

15

Digital input 15

29

16

Digital input 16

30

L-

Reference pole

20

17 18 19

11 12 13 14 15 16

11 12 13 14

1

LS+

L-

DI

2 3 4 5 6 7 8

15 16

17 18 19 20

30

27 28 29

21 22 23 24 25 26

21 22 23 24

1

LS+

L-

DI

2 3 4 5 6 7 8

25 26

27 28 29 30

40

37 38 39

31 32 33 34 35 36

31 32 33 34

1

LS+

L-

DI

2 3 4 5 6 7 8

35 36

37 38 39 40