GuardPLC 1800 Controllers 9

Rockwell Automation Publication 1753-IN002C-EN-P - June 2010

LS+, not L+, should be used for short-circuit protection. Each LS+ features individual
short-circuit and EMC protection that make it important to use LS+ for only its eight related
inputs.

Line Control

The short-circuit and line break monitoring system, such as E-stop inputs, cannot be configured
for the GuardPLC 1800 controller. This is due to the fact that the 24 discrete inputs are actually
analog inputs with a resolution of one bit.

Safety-Related Analog Inputs

The controller has 8 analog inputs with transmitter supplies for the unipolar measurement of
voltages from 0…10V, referenced to L-. A 10 K

Ω

shunt is used for single-ended voltage signals.

With a 500

Ω

shunt resistor, currents from 0…20 mA can also be measured.

The feeder lines should be no more than 300 m (984 ft) in length. Use shielded, twisted-pair
cables, with the shields connected at both ends, for each measurement input.

Unused analog inputs must be short-circuited. Place wire jumpers into any inputs that are not
used.

31

LS+

Sensor supply for inputs 17…24

32

17

Digital input 17

33

18

Digital input 18

34

19

Digital input 19

35

20

Digital input 20

36

21

Digital input 21

37

22

Digital input 22

38

23

Digital input 23

39

24

Digital input 24

40

L-

Reference pole

Terminal Number

Designation

Function

AI

T1 I1 L- T2 I2 L-

41 42 43 44 45 46

Wire Jumper

Wire Jumper

Advertising
This manual is related to the following products: