22 GuardPLC 1800 Controllers

Rockwell Automation Publication 1753-IN002C-EN-P - June 2010

Counters

Number of counters

2 (not electrically isolated)

Inputs

3 per counter (A, B, Z)

Input voltages

5V and 24V DC

High signal (5V DC): 4…6V
High signal (24V DC): 13…33V
Low signal (5V DC): 0…0.5V
Low signal (24V DC): -3…5V

Input currents

1.4 mA @ 5V DC
6.5 mA @ 24V DC

Input impedance

3.7 k

Ω

Counter resolution

24-bit

Input frequency, max

100 kHz

Triggered

on negative edge

Edge steepness

1 V/

μ

s

Pulse duty factor

1:1

Analog Inputs

Number of inputs

8 (unipolar, not electrically isolated)

External shunt
(for current measurement)

500

Ω

for 0…20 mA

Input values related to L-

Nominal Value: 0…10V DC or 0…20 mA with 500

Ω

shunt

Service Value: -0.1…11.5V DC or -0.4…23 mA with 500

Ω

shunt

Input impedance

1 M

Ω

Internal resistance of the
signal source

500

Ω

Overvoltage protection

+15V, -4V

Resolution (A/D converter)

12-bit

Accuracy

0.1% @ 25 °C (77 °F)
0.5% @ 60 °C (140 °F)

Transmitter supplies

25.37…28.24V /

46 mA, short-circuit proof

Safety accuracy

± 2%

(1)

Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and
Grounding Guidelines, publication

1770-4.1

.