Rockwell Automation 1790D-XXXX DeviceNet Digital Base Terminal Block CompactBlock LDX I/O Series B User Manual

Page 26

Advertising
background image

26 DeviceNet Digital Base Terminal Block CompactBlock LDX I/O

Publication

1790-IN012B-EN-P - July 2008

ESD immunity

IEC 61000-4-2:

8 kV air discharges

Radiated RF
immunity

IEC 61000-4-3:

10V/m with 1 kHz sine-wave 80%AM from 80…1000 MHz

10V/m with 1 kHz sine-wave 80%AM from 1.4…2 GHz

10V/m with 200 Hz 50% Pulse 100%AM at 900 MHz

EFT/B immunity

IEC 61000-4-4:

±2 kV at 5 kHz on signal ports

±2 kV at 5 kHz on communications ports

Surge transient
immunity

IEC 61000-4-5:

±1 kV line-line(DM) and ±2 kV line-earth(CM) on signal ports

±2 kV line-earth(CM) on communications ports

Conducted RF
immunity

IEC 61000-4-6:

10V rms with 1 kHz sine-wave 80%AM from 150 kHz…80 MHz

Environmental

Attribute