Install the base block, Set the node address – Rockwell Automation 1790D-XXXX DeviceNet Digital Base Terminal Block CompactBlock LDX I/O Series B User Manual
Page 6
 
6 DeviceNet Digital Base Terminal Block CompactBlock LDX I/O
Publication
1790-IN012B-EN-P - July 2008
versions of the blocks. For example, for the EDS file for 
1790D-T8BV8B blocks, use the EDS file labelled 1790D-8BV8B.
Install the Base Block
To install the base block:
•
set the node address on the base block.
•
mount the base block.
•
mount the optional expansion blocks.
•
wire the terminal block.
•
connect the DeviceNet cable.
Set the Node Address
When setting the node address on the base block, note that each base 
block comes with its internal program set for node address 63. To 
reset the node address, adjust the switches on the front of the base 
block. The two switches are most significant digit (MSD) and least 
significant digit (LSD). You can set switches to 00...63. 
Node Address Example
The base block reads the rotary switches only when power is 
applied. Switch settings 64…99 cause the base block to use the last 
valid node address stored internally.
You can also set the node address through RSNetWorx for DeviceNet 
software or a similar configuration tool. 
When you use software configuration for the node address, set the 
switches to 64…99.
In this 
example, the 
node address 
setting is 11. 
MSD
LSD
NODE ADDRESS
MOD NET
STATUS
44202